Safe wire sizing for your vehicle electrical system

Understanding Voltage Drop: Why Wire Length Matters

Understanding Voltage Drop: Why Wire Length Matters

Voltage drop is the #1 most misunderstood concept in vehicle electrical systems. It’s why your lights are dim, your winch pulls weak, and your fridge stops cooling even though everything is “wired correctly.”

What is Voltage Drop?

When electricity flows through a wire, the wire resists that flow. This resistance causes some voltage to be “lost” as heat before it reaches your device.

Think of it like water pressure in a hose:

  • Short, thick hose = full pressure at the end
  • Long, thin hose = reduced pressure at the end
  • Same principle applies to electrical wires

The Formula (Don’t Panic)

Voltage drop is calculated using Ohm’s Law:

Voltage Drop = Current × Resistance × Length

Where:

  • Current = Amps your device draws
  • Resistance = Ohms per foot (wire gauge specific)
  • Length = TOTAL circuit length (power wire + ground wire)

Important: You must account for BOTH the power wire and ground wire. If you run 15 feet of wire to your device, the total circuit is 30 feet (15 feet there, 15 feet back).

Why 3-5% is the Standard

The automotive industry recommends keeping voltage drop under 5% for most accessories, and under 3% for sensitive electronics.

Here’s why:

At 3% Voltage Drop:

  • 12V system: You lose 0.36V (device gets 11.64V)
  • Effect: Barely noticeable to most devices
  • Best for: Radios, GPS, sensitive electronics

At 5% Voltage Drop:

  • 12V system: You lose 0.6V (device gets 11.4V)
  • Effect: Slightly dimmer lights, slightly slower motors
  • Acceptable for: LED lights, accessories, most equipment

At 10% Voltage Drop:

  • 12V system: You lose 1.2V (device gets 10.8V)
  • Effect: Noticeably dimmer lights, weak winch performance
  • Sometimes okay for: Non-critical loads where performance loss is acceptable

Over 10% Voltage Drop:

  • 12V system: You lose 1.2V+ (device gets <10.8V)
  • Effect: Severe performance degradation, potential damage
  • Never acceptable

Real-World Examples

Example 1: Light Bar (The Classic Problem)

Scenario:

  • 150W LED light bar = 12.5A at 12V
  • Mounted on roof, 20 feet from battery
  • Using 12 AWG wire

Calculation:

  • Total length: 20 ft × 2 = 40 ft
  • 12 AWG resistance: 0.00159 ohms/ft
  • Total resistance: 40 ft × 0.00159 = 0.0636 ohms
  • Voltage drop: 12.5A × 0.0636 = 0.795V
  • Percentage: 0.795V / 12V = 6.6% voltage drop

Result: Your light bar is noticeably dimmer than it should be. You’re only getting about 93% of its potential brightness.

Solution: Upgrade to 10 AWG wire

  • 10 AWG resistance: 0.000999 ohms/ft
  • New voltage drop: 12.5A × (40 × 0.000999) = 0.5V = 4.2%
  • Much better! Now you’re getting 96% brightness.

Example 2: Winch (High Current, Critical Performance)

Scenario:

  • 9,000 lb winch = 300A peak draw
  • 15 feet from battery
  • Using 2 AWG wire

Calculation:

  • Total length: 15 ft × 2 = 30 ft
  • 2 AWG resistance: 0.000156 ohms/ft
  • Total resistance: 30 ft × 0.000156 = 0.00468 ohms
  • Voltage drop: 300A × 0.00468 = 1.4V
  • Percentage: 1.4V / 12V = 11.7% voltage drop

Result: Your winch is significantly weaker than rated. At full load, you’re losing over 1 volt.

Solution: Upgrade to 2/0 AWG wire

  • 2/0 resistance: 0.0000779 ohms/ft
  • New voltage drop: 300A × (30 × 0.0000779) = 0.7V = 5.8%
  • Better, but still losing some pulling power. For critical winch recovery, some people go even thicker.

Example 3: Fridge (Long Run, Moderate Current)

Scenario:

  • 50W fridge = 4.2A at 12V
  • Mounted in rear of vehicle, 25 feet from auxiliary battery
  • Using 16 AWG wire

Calculation:

  • Total length: 25 ft × 2 = 50 ft
  • 16 AWG resistance: 0.00402 ohms/ft
  • Total resistance: 50 ft × 0.00402 = 0.201 ohms
  • Voltage drop: 4.2A × 0.201 = 0.84V
  • Percentage: 0.84V / 12V = 7% voltage drop

Result: Your fridge is struggling. Low voltage can cause the compressor to run inefficiently or shut off entirely.

Solution: Upgrade to 12 AWG wire

  • 12 AWG resistance: 0.00159 ohms/ft
  • New voltage drop: 4.2A × (50 × 0.00159) = 0.33V = 2.8%
  • Perfect! Your fridge gets proper voltage and runs efficiently.

The Hidden Cost of Voltage Drop

Beyond poor performance, excessive voltage drop costs you:

1. Energy Waste

Lost voltage becomes heat in the wire. You’re literally burning energy (and battery capacity) before it reaches your device.

2. Shortened Accessory Life

Many devices are rated for 12V. Running them at 10.5V due to voltage drop puts stress on electronics and motors, shortening their lifespan.

3. Battery Drain

Your device draws more current to compensate for low voltage, draining your battery faster.

4. False Troubleshooting

“My light bar is defective” - No, it’s just not getting enough voltage.

How to Measure Voltage Drop

You need a multimeter and a helper:

  1. Turn on the device (light bar, winch, etc.)
  2. Measure voltage at battery terminals - should read ~12.6V
  3. Measure voltage at device terminals - should read close to battery voltage
  4. Calculate the difference - this is your voltage drop
  5. Divide by battery voltage - this is your percentage

Example:

  • Battery: 12.6V
  • Device: 11.8V
  • Drop: 0.8V
  • Percentage: 0.8 / 12.6 = 6.3% voltage drop

If you see over 5%, you need thicker wire or shorter runs.

Common Misconceptions

Myth #1: “If the wire doesn’t get hot, it’s fine”

False. Wire can handle the current without overheating but still have excessive voltage drop. These are two separate issues.

Myth #2: “Just use the biggest wire you can afford”

Partially true. There are diminishing returns. Going from 12 AWG to 10 AWG makes a big difference. Going from 4 AWG to 2 AWG on a 10A circuit is overkill.

Myth #3: “Voltage drop only matters for lights”

False. Every electrical device suffers from voltage drop. Motors work harder, electronics get stressed, batteries drain faster.

Myth #4: “I only need to worry about the power wire”

False. The ground wire carries the same current and has the same resistance. Size both wires equally.

Quick Reference: Voltage Drop by Wire Gauge

Here’s how much voltage you lose per 100 feet of TOTAL circuit length (50 ft power + 50 ft ground) at various amperage levels:

Wire Gauge10A20A30A50A100A
22 AWG1.61V (13.4%)3.22V (26.8%)---
18 AWG0.64V (5.3%)1.28V (10.7%)1.92V (16%)--
14 AWG0.25V (2.1%)0.51V (4.2%)0.76V (6.3%)1.27V (10.6%)-
12 AWG0.16V (1.3%)0.32V (2.7%)0.48V (4%)0.80V (6.6%)1.59V (13.3%)
10 AWG0.10V (0.8%)0.20V (1.7%)0.30V (2.5%)0.50V (4.2%)1.00V (8.3%)
6 AWG0.04V (0.3%)0.08V (0.7%)0.12V (1%)0.20V (1.6%)0.40V (3.3%)
2 AWG0.016V (0.1%)0.031V (0.3%)0.047V (0.4%)0.078V (0.7%)0.156V (1.3%)

Values shown for 12V system. Highlighted cells show acceptable voltage drop (<5%).

The Solution

Use Wire Solved’s calculator to factor in both amperage AND length. It automatically:

  • Calculates total circuit resistance
  • Computes voltage drop percentage
  • Recommends proper wire gauge
  • Explains why if an upgrade is needed

What’s Next?

Now that you understand voltage drop:

Ready to size your wire?

Use our free calculator to get instant recommendations based on your specific setup.

Try the Calculator